As a tilt sensor,
what angle change does it respond to ie 2degrees 5degrees 15degrees
does it reset its start datum every time it is reset
as a vibration sensor, is its sensitivity adjustable ie ie high, standard low
Regards: Frank
what angle change does it respond to ie 2degrees 5degrees 15degrees
does it reset its start datum every time it is reset
as a vibration sensor, is its sensitivity adjustable ie ie high, standard low
Regards: Frank
Question by: frank S on Sep 21, 2018, 12:22 PM
When the switch is in SHOCK detection (DIP2 off), the detector works in shock / vibration mode;
TILT detection mode is selected by switching it to the TILT position (DIP2 on).
The NORM / CONFIRM (DIP1) switch only has a function in SHOCK mode. It allows you to set weather the detector should be activated by one (NORM DIP1 on) or two consecutive shocks (CONFIRM DIP1 off).
If the shock confirmation mode is active, the first detection (pre-alarm) triggers a 10 s interval of inactivity and detection of the second (confirmatory) alarm is activated after this period. The second alarm must be activated within 30 s, otherwise the pre-alarm is erased.
The trimmer is used to set the shock/tilt sensitivity. The maximum sensitivity is to the right, the minimum is to the left.
When in tilt detection mode, the detector reacts to changes in its position. It is recommended to install the detector in a vertical position if possible.
Tillt detection 10° - 45°.
Regards
TILT detection mode is selected by switching it to the TILT position (DIP2 on).
The NORM / CONFIRM (DIP1) switch only has a function in SHOCK mode. It allows you to set weather the detector should be activated by one (NORM DIP1 on) or two consecutive shocks (CONFIRM DIP1 off).
If the shock confirmation mode is active, the first detection (pre-alarm) triggers a 10 s interval of inactivity and detection of the second (confirmatory) alarm is activated after this period. The second alarm must be activated within 30 s, otherwise the pre-alarm is erased.
The trimmer is used to set the shock/tilt sensitivity. The maximum sensitivity is to the right, the minimum is to the left.
When in tilt detection mode, the detector reacts to changes in its position. It is recommended to install the detector in a vertical position if possible.
Tillt detection 10° - 45°.